상단으로 상단으로

 Integrated SHDDC Main Board (NTC)

Integrated SHDDC Main Board (NTC)

SHDDC-M2

  • Power 24VDC
  • Contact Input 16port,Contact Output 16port
  • Analog Multi Function Input 8port
  • Analog Output 4port (0-10V/0-20mA)
  • Analog SSR Output 1port (24VDC)
  • Communication port (RS485 Modbus RTU) X 4

Overview and Features

Smart Hybrid DDC – Advanced Programmable Controller
The Smart Hybrid DDC is an innovative programmable controller that integrates the advantages of MICOM and PLC technologies. It enables the implementation of universal program logic, making it a cost-effective solution for various control applications while ensuring easy programming and maintenance.

- Versatile Input and Output Compatibility
Supports voltage, current, RTD, and thermistor inputs for diverse control requirements.
- User-Friendly Programming
Utilizes the widely adopted Ladder Diagram (LD) language, allowing easy program modifications and simple maintenance using Logic Studio.
- Seamless System Integration
Compatible with existing control systems through the MODBUS RTU protocol.
Supports Ethernet, CDMA, and Bluetooth with the addition of an optional communication card.
- Modular Expandability & Flexible Installation
Can be expanded on a modular basis via communication lines, ensuring flexible panel layouts and remote installation capability.
- Built-in PID Control for Precision
Equipped with an 8-channel PID function with Auto-Tuning for precise and efficient control.
- Compact and Economical Design
Provides optimized input and output specifications for unit equipment control, offering a space-saving and cost-efficient solution.

Specification

SPEC SHDDC-M1 SHDDC-M2
Power 24V AC/DC (DC Min 1.0A) 24V AC/DC (DC Min 1.0A)
MCU 32bit RISC 32bit RISC Processor
RTC Built-in Built-in
Comm. 4ch RS-485 (Master/Slave) / Micro USB (PC) 4ch RS-485 (Master/Slave) / Micro USB (PC)
Control FIND 4 digit / Tact s/w 4EA FIND 4 digit / Tact s/w 4EA)
DI 16points (24V DC Source) 16points (24V DC Source)
DO 16points (Relay Dry Contact) 16points (Relay Dry Contact)
SSR 1points (24V DC) 1points (24V DC)
AI 7ch (PT100 / 0-10V / 0-20mA)
1ch (0-10V / 0-20mA)
1ch (CT)
5ch (Thermistor / 0-10V / 0-20mA)
2ch (PT100 / 0-10V / 0-20mA)
1ch (0-10V / 0-20mA)
1ch (CT)
AO 4ch (0-10V / 0-20mA) 4ch (0-10V / 0-20mA)

List