Differential Pressure Airflow & Velocity Sensor

Differential Pressure Airflow & Velocity Sensor

DPS-PQ-125

  • Wall-mounted precision differential pressure sensor (–1500 Pa to +1500 Pa)
  • 24 VDC power input
  • RS-485 communication (Modbus RTU, 1 channel), 1 digital contact output
  • 3 input switches, 5-digit segment display
  • User-configurable alarm output
  • One-touch wiring and splash-proof housing

Overview and Features

Displays differential pressure in air and provides control contacts and transmission outputs based on the measured value.
Suitable for hospitals, cleanrooms, and industrial environments where positive or negative pressure must be maintained.
Also used in HVAC systems to monitor filter condition and determine replacement timing.

Specification

Items DPS-AQ-1K5 DPS-PQ-1K5 DPS-PQ-125
Power Supply (VAC) 24VDC [±20%] / 80mA (Standby) [Fixed 24V Input]
Pressure Measurement Range  -1500.0 ~ 1500.0 Pa / -152.95 ~ 152.95 mmAq -125.0 ~ 125.0 Pa / -12.74 ~ 12.74 mmAq
Module Type Sensirion SDP33 Sensirion SDP32
Built-in Differential Pressure Sensor Sensirion Digital Differential Pressure Sensor (Measurement range: -40℃ ~ 85℃)
Allowable Overpressure 1 Bar (P-max)
Burst Pressure 3 Bar (P-burst)
Display 5-digit 7-segment display
Input Switch 3 Tact Switches ('DOWN', 'SET', 'UP')
Output Port • Digital Output Relay 1 Port (NO / COM / NC)
• Condition-based control output (220VAC / 5A) **
• Analog Output Current 1 Port (4–20mA)
• Condition-based conversion output **
Monitoring Communication Port (Slave) • MODBUS RS-485 communication 1 port (isolated / D+, D-, GND)
• Communication protocol: MODBUS RS-485 RTU
• Address: 1 ~ 254 (default: 1)
• Baud rate: selectable (9,600 / 19,200 / 38,400 / 115,200 bps, default: 38,400 bps)
Operating Temperature (℃) -10 ~ 50℃
Storage Temperature (℃) -20 ~ 60℃
Ingress Protection IP54 or higher (when cover is properly fastened)

** Selectable output mode: Air velocity / Airflow / Differential pressure can be selected via the user menu settings.

Items SDP33 (±1500 Pa) SDP32 (±125 Pa)
Differential Pressure Spac Measurement range -1500.0 ~ 1500.0 Pa (-6 ~ 6 inches H2O) 152.95 ~ 152.95 mmAq -125.00 ~ 125.00 Pa (-0.5 ~ 0.5 inch H2O)-12.746 ~ 12.746 mmAq
Zero point accuracy 0.2 Pa 0.08 Pa
Span accuracy 3% of reading (±500Pa) 6% of reading (±1500Pa) 3% of reading
Zero point repeatability 0.1 Pa 0.025 Pa
Span repeatability 0.5% of reading (±500Pa) 3% of reading (±1500Pa) 0.5% of reading
Span shift due to temperature variation < 1% of reading per 10℃ < 0.5% of reading per 10℃
Offset stability < 0.03 Pa / year < 0.01 Pa / year
Resolution 16 bit
Calibrated for Air, N2
Media compatibility Air, N2, O2, non-condensing
Temperature Spac Measurement range -40℃ ~ 85℃
Accuracy 2 ℃ (-10℃ ~ 60℃) / 3 ℃ (-40℃ ~ 85℃)
Repeatability 0.1 ℃