상단으로 상단으로

AHU / PACKAGED Air conditioner

AHU / PACKAGED Air conditioner

STHAV-MB

  • Power supply 100 to 240 VAC
  • 16-port contact input, 16-port contact output, 1-port (SSR)
  • Analog input x3, Analog output x4
  • Communication port (RS485 Modbus RTU) X 4
  • RTC (Schedule Operation) - Options

Overview and Features

As a configurable controller using a high-performance microprocessor, it can control cooling, heating, humidification, and dehumidification, and provides analog outputs (voltage, current) according to field conditions, making it easy to control inverters, cooling and heating valves, and provides external monitoring communication protocols as a general-purpose protocol (MODBUS RTU) so that users can easily link to HMI or web servers. In addition, it is equipped with various protection functions for extending the life and protection of the compressor, so it can be controlled more safely, and according to the option, it is designed to remember the situation at the time of the alarm, helping users to maintain quickly and easily.

[Features]
- Built-in heating 5 steps (including SR), cooling (dehumidification) 3 steps, humidification (Pan type 2 steps, vaporization, electrode seal)
- External Monitoring (MODBUS RTU Protocol) Communication 2ch
- Body/Remote Display (Seungil Protocol) Communication 2ch
- Free Voltage (100-240V) is available with SMPS application
- Remote monitoring via TCP/IP (optional)



Specification

Power Input power 100-240VAC 50/60Hz
Micom MCU ATmega2560
Digital input Input port 16 points (24VDC) / 1 point (Full of Water)
Digital output Output port 16 points / 1points (SSR)
Output method Relay contact / PWM
Relay rating 250V 3A / 24VDC
Analog input Temperature sensor 1ch (PT100Ω)
Humidity sensor 1ch (0-3VDC)
CT sensor 1ch
Analog output -
Load resistance -
Communication Communication port 4ch
Communication address 1~99
Communication speed 9600, 19200bps
Parity bit None
Stop bit 1bit
Communication distance Maximum 1.2km (May decrease depending on the environment)
Protocol MODBUS RTU(1ch), SEUNGIL(2ch)
RTC Schedule driving -
Enviroment Operating temperature/humidity -10~50℃, 5~95% (No condensation)
Storage temperature -20~60℃

List